Skip to main content

D.C. Compound Generators in Parallel

Consider two compound generators 1 and 2 running in parallel as shown in the Fig. 1.
Fig. 1
       As the voltage characteristics for the usual compound generators are rising, their parallel operation is unstable in the absence of corrective devices.
       Let us consider that each generator is taking proper share of load. If for some reason, the generator 1 takes increased load slightly then the current passing through its series field winding increases strengthening its field to increase the generated e.m.f. This causes generator 1 to take still more load. If system load is assumed to be constant then the load on generator 2 will decrease weakening its series field due to less current passing through its field winding which results in further decrease in its load. This effect is cumulative which leads generator 1 to take the entire load and generator 2 will be driven as motor. The circuit breakers of at least one of the two generators will open to stop the parallel operation. The under compound generators show stable operation like shunt generators.
       For stable parallel operation of over and level compound generators, equalizer bus bars are used. It is connected to the armature ends of the series coils of the generators. The equalizer bus bar is also a conductor which is not required is case of under compound generator as their characteristics are not rising.
       Now consider that the same two compound generators are operating in parallel with equalizer bar between them. If for any reason, generator 1 starts taking more load than its proper share the its series field current is increased. But now this increased field current will partly pass through series field winding of generator 1 and partly through series field winding of generator 2 via equalizer bar. Thus the two generators are affected in similar way preventing generator 1 from taking extra load. To have proper division of load from no load to full load it is required that the regulation of each generator must be same. The series field resistances should be inversely proportional to the generator ratings.

Comments

Popular posts from this blog

Practical Commutation

The e.m.f. induced in each coil of armature is alternating in nature. If load is connected, the current flowing will also be alternating. But the flow of current in a d.c. generator must be undirectional. This can be achieved by the use of commutator. When the armature conductors are under the influence of one pole they carry current in one direction whereas the current is reversed when the conductors are under the influence of other pole. This reversal of current takes place along the magnetic neutral axis. Fig. 1 Note : The reversal of current is likely to take place in short interval when a coil is short circuited by a brush so that transfer of current from one direction to other is carried out without any sparking. This process is called commutation.        Thus a process by which current in the short circuited coil is reversed while it crosses the MNA is called commutation. The time during which the coil remains short circuited is known as...

Demagnetising and Cross Magnetizing Conductors

The conductors which are responsible for producing demagnetizing and distortion effects are shown in the Fig.1. Fig. 1        The brushes are lying along the new position of MNA which is at angle θ  from GNA. The conductors in the region AOC = BOD = 2θ  at the top and bottom of the armature are carrying current in such a direction as to send the flux in armature from right to left. Thus these conductors are in direct opposition to main field and called demagnetizing armature conductors.         The remaining armature conductors which are lying in the region AOD and BOC carry current in such a direction as to send the flux pointing vertically downwards i.e. at right angles to the main field flux. Hence these conductors are called cross magnetizing armature conductors which will cause distortion in main field flux.        These conductors are shown in the Fig. 2 Fig. 2  ...

Winding Pitches

Now we will consider the definitions of different types of winding pitches, required in the design of the armature winding. 1.1 Back Pitch         The distance which is measured interns of armature conductors i.e. between top and bottom coil sides of a coil measured around the back of the armature i.e. away from the commutator is called back pitch and is denoted by . It is measured interms of coil sides. Note : Since it is difference between odd and even number, it is always odd number.        The size of the coil is decided by the back pitch. The back pitch is normally equal to coilsides per pole. It is shown for lap and wave type of winding in the Fig. 1. Fig. 1        The back pitch for the winding shown in the Fig. 1 is y b = 14 - 1 = 13 as coilsides 1and 14 are of coil number 1. 1.2 Front Pitch        It is defined as the distance measured between two c...