EXACT VOLTAGE DROP

In Figure 1.40, the exact voltage drop is AH instead of AG. During calculation of approximate voltage drop, AG has already been calculated. If GH is being added to AG, the exact voltage drop can be obtained.
Consider the right-angled triangle OCG. We have
OC2 = OG2 + GC2
i.e. OC2OG2 = GC2
i.e. (OCOG)(OC + OG) = GC2
i.e. (OHOG)(OC + OG) = GC2
i.e. GH.2.OC= GC2     [Taking OCOG]
i.e.   images
For lagging power factor, the exact voltage drop is
images
For leading power factor, the exact voltage drop is given by
images
In general, the voltage drop is
images
and percentage voltage drop is
images
images
It may be noted that the upper sign is to be used for lagging power factor and the lower sign for leading power factor.
Example 1.11 The OC and SC tests on a 300/600 V, 50 Hz, single-phase transformer gave the fol-lowing results:
OC test (LV side): 300 V, 0.8 A, 70 W
SC test (HV side): 20 V, 12 A, 90 W
where LV and HV is low voltage and high voltage, respectively.
Find the equivalent circuit of the transformer referred to as LV side and also calculate the secondary voltage when delivering 6 kW at 0.8 p.f. (power factor) lagging.
Solution
OC test (LVside):
Instruments are placed on LV side and HV side is kept open.
V1 = 300 V, I0 = 0.8 A, W0 = 70 W
Now,   images
∴    IW= I0cosθ0=0.8×0.292=0.2336A
and   Iμ=I0sinθ0=0.8×0.956=0.7648A
∴   images
SC test:
Instruments are placed on HV side and LV side is kept open.
images
VSC = 20 V, ISC = 12 A, PSC = 90 W
images
images
Figure E1.2
∴      images
∴      images
∴      images
∴      images
The equivalent circuit referred to as LV side is shown in Figure E1.2.
∴      images
Approximate voltage drop referred to as secondary for 0.8 power factor lagging is
=I2(R02cosθ+X02sinθ
=12.5×(0.625×0.8+1.548×0.6)=17.86 V
∴      Secondary terminal voltage = 600 – 17.86 = 582.14 V (approx.)

Comments

Popular posts from this blog

Practical Commutation

The e.m.f. induced in each coil of armature is alternating in nature. If load is connected, the current flowing will also be alternating. But the flow of current in a d.c. generator must be undirectional. This can be achieved by the use of commutator. When the armature conductors are under the influence of one pole they carry current in one direction whereas the current is reversed when the conductors are under the influence of other pole. This reversal of current takes place along the magnetic neutral axis. Fig. 1 Note : The reversal of current is likely to take place in short interval when a coil is short circuited by a brush so that transfer of current from one direction to other is carried out without any sparking. This process is called commutation.        Thus a process by which current in the short circuited coil is reversed while it crosses the MNA is called commutation. The time during which the coil remains short circuited is known as...

Demagnetising and Cross Magnetizing Conductors

The conductors which are responsible for producing demagnetizing and distortion effects are shown in the Fig.1. Fig. 1        The brushes are lying along the new position of MNA which is at angle θ  from GNA. The conductors in the region AOC = BOD = 2θ  at the top and bottom of the armature are carrying current in such a direction as to send the flux in armature from right to left. Thus these conductors are in direct opposition to main field and called demagnetizing armature conductors.         The remaining armature conductors which are lying in the region AOD and BOC carry current in such a direction as to send the flux pointing vertically downwards i.e. at right angles to the main field flux. Hence these conductors are called cross magnetizing armature conductors which will cause distortion in main field flux.        These conductors are shown in the Fig. 2 Fig. 2  ...

Armature Voltage Control Method or Rheostatic Control of dc motor

Speed Control of D.C. Shunt Motor (Part2)  2. Armature Voltage Control Method or Rheostatic Control        The speed is directly proportional to the voltage applied across the armature. As the supply voltage is normally constant, the voltage across the armature can be controlled by adding a variable resistance in series with the armature as shown in the Fig. 1. Fig. 1 Rheostat control of shunt motor        The field winding is excited by the normal voltage hence I sh is rated and constant in this method. Initially the reheostat position is minimum and rated voltage gets applied across the armature. So speed is also rated. For a given load, armature current is fixed. So when extra resistance is added in the armature circuit, I a remains same and there is voltage drop across the resistance added ( I a R). Hence voltage across the armature decreases, decreasing the speed below normal value. By varyi...