CONSERVATOR AND BREATHER

Satisfactory operation of a transformer solely depends on the condition of the oil. It is required to keep the oil clean and dry. With the rise of temperature, the oil level increases. Rise of temperature depends on the load of the transformer. If load increases, oil expands. If load decreases, contraction of oil occurs. Since smaller transformers are not totally filled by oils, some space is left between tank walls and oil, which is occupied by air. The tank is connected to the atmosphere through a vent pipe. Air is expelled out if oil expands. Air is drawn from the atmosphere if oil contracts. When air enters the transformer, it is required to extract moisture from the air. An apparatus known as breather is used to extract moisture from the air. It is a small container connected to the vent pipe containing a dehydrating material such as silica gel crystal impregnated with cobalt chloride. The colour of the material is blue when it is dry. It becomes whitish pink when it is damp. In front of the container, a glass window is provided to observe the colour of the material.
If the transformer becomes overloaded, it overheats the oil and sludge formation occurs in the presence of air. If transformer suffers short circuit, temperature rise becomes very high and this causes vaporization of a part of the oil, which forms an explosive mixture with air. This explosive mixture can ignite and cause considerable damage. To prevent the air coming in contact with air as well as moisture, conservators are used. It takes the responsibility of expansion and contraction of oil without allowing it to come into contact with air. The conservator is an air-tight cylindrical drum mounted on or near the cover of the transformer. It is connected to the transformer through a small pipe. In Figure 1.18, breather and conservator are shown.

Comments

Popular posts from this blog

Practical Commutation

The e.m.f. induced in each coil of armature is alternating in nature. If load is connected, the current flowing will also be alternating. But the flow of current in a d.c. generator must be undirectional. This can be achieved by the use of commutator. When the armature conductors are under the influence of one pole they carry current in one direction whereas the current is reversed when the conductors are under the influence of other pole. This reversal of current takes place along the magnetic neutral axis. Fig. 1 Note : The reversal of current is likely to take place in short interval when a coil is short circuited by a brush so that transfer of current from one direction to other is carried out without any sparking. This process is called commutation.        Thus a process by which current in the short circuited coil is reversed while it crosses the MNA is called commutation. The time during which the coil remains short circuited is known as...

Demagnetising and Cross Magnetizing Conductors

The conductors which are responsible for producing demagnetizing and distortion effects are shown in the Fig.1. Fig. 1        The brushes are lying along the new position of MNA which is at angle θ  from GNA. The conductors in the region AOC = BOD = 2θ  at the top and bottom of the armature are carrying current in such a direction as to send the flux in armature from right to left. Thus these conductors are in direct opposition to main field and called demagnetizing armature conductors.         The remaining armature conductors which are lying in the region AOD and BOC carry current in such a direction as to send the flux pointing vertically downwards i.e. at right angles to the main field flux. Hence these conductors are called cross magnetizing armature conductors which will cause distortion in main field flux.        These conductors are shown in the Fig. 2 Fig. 2  ...

Winding Pitches

Now we will consider the definitions of different types of winding pitches, required in the design of the armature winding. 1.1 Back Pitch         The distance which is measured interns of armature conductors i.e. between top and bottom coil sides of a coil measured around the back of the armature i.e. away from the commutator is called back pitch and is denoted by . It is measured interms of coil sides. Note : Since it is difference between odd and even number, it is always odd number.        The size of the coil is decided by the back pitch. The back pitch is normally equal to coilsides per pole. It is shown for lap and wave type of winding in the Fig. 1. Fig. 1        The back pitch for the winding shown in the Fig. 1 is y b = 14 - 1 = 13 as coilsides 1and 14 are of coil number 1. 1.2 Front Pitch        It is defined as the distance measured between two c...