Synchronous Condensers

When synchronous motor is over excited it takes leading p.f. current. If synchronous motor is on no load, where load angle δ is very small and it is over excited (Eb > V) then power factor angle increases almost upto 90o. And motor runs with almost zero leading power factor condition. This is shown in the phasor diagram Fig. 1.

Fig. 1 Synchronous condenser
       This characteristics is similar to a normal capacitor which takes leading power factor current. Hence over excited synchronous motor operating on no load condition is called as synchronous condenser or synchronous capacitor. This is the property due to which synchronous motor is used as a phase advancer or as power improvement device.
1.1 Disadvantage of Low Power Factor
       In various industries, many machines are of induction motor type. The lighting and heating loads are supplied through transformers. The induction motors and transformers draw lagging current from the supply. Hence the overall power factor is very low and lagging in nature.
       The power is given by,
                       P = VI cosΦ                                         .............. single phase
...                     I = P/(VcosΦ)
       The supply voltage is constant and hence for supplying a fixed power P, the current is inversely proportional to the p.f. cosΦ. Let P = KW is to be supplied with a voltage of 230 V then,
Case i) cosΦ = 0.8,
                   I = (5 x103)/(230 x 0.8) = 27.17 A
Case ii) cos = 0.6,

                   I = (5 x103)/(230 x 0.6) = 36.23 A
       Thus as p.f. decreases, becomes low, the current drawn from the supply increases to supply same power to the load. But if p.f. maintained high, the current drawn from supply is less.
       The high current due to low p.f. has following disadvantages :
1. For higher current, conductor size required is more which increases the cost.
2. The p.f. is given by
                    cosΦ = Active power/ Apparent = (P in KW)/ (S i.e. KVA rating)
       Thus for fixed active power P, low p.f. demands large KVA rating alternators and transformers. This increases the cost.
3. Large current means more copper losses and poor efficiency.
4. Large current causes large voltage drops in transmission lines, alternators and other equipments. This results into poor regulation. To compensate such drop extra equipments is necessary which further increases the cost.
Note : Hence power factor improvement is must practice. Hence the supply authorities encourage consumers to improve the p.f.
1.1 Use of Synchronous Condenser in Power Factor Improvement
       The low power factor increases the cost of generation, distribution and transmission of the electrical energy. Hence such low power factor needs to be corrected. Such power factor correction is possible by connecting synchronous motor across the supply and operating it on no load with over excitation.
       Now let Vph is the voltage applied and I1ph is the current lagging Vph by angle Φ1. This power factor Φ1 is very low, lagging.
       The synchronous motor acting as a synchronous condenser is now connected across the same supply. This draws a leading current of I2ph.
       The total current drawn from the supply is now phasor of Iph and I2ph. This total current IT now lags Vph by smaller angle Φ due to which effective power factor gets improved. This is shown in the Fig. 2.
Fig. 2  Power factor correction by synchronous condenser

       This is how the synchronous motor as a synchronous condenser is used to improve power factor of the combined load.

Comments

Popular posts from this blog

Transformer multiple choice questions part 1

Hello Engineer's Q.[1] A transformer transforms (a) frequency (b) voltage (c) current (d) voltage and current Ans : D Q.[2] Which of the following is not a basic element of a transformer ? (a) core (b) primary winding (c) secondary winding (d) mutual flux. Ans : D Q.[3] In an ideal transformer, (a) windings have no resistance (b) core has no losses (c) core has infinite permeability (d) all of the above. Ans : D Q.[4] The main purpose of using core in a transformer is to (a) decrease iron losses (b) prevent eddy current loss (c) eliminate magnetic hysteresis (d) decrease reluctance of the common magnetic circuit. Ans :D Q.[5] Transformer cores are laminated in order to (a) simplify its construction (b) minimize eddy current loss (c) reduce cost (d) reduce hysteresis loss. Ans : B Q.[6] A transformer having 1000 primary turns is connected to a 250-V a.c. supply. For a secondary voltage of 400 V, the number of secondary turns should be (a) 1600 (b) 250 (c) 400 (d) 1250 A

Condition for Maximum Power Developed In Synchronous Motor

The value of δ for which the mechanical power developed is maximum can be obtained as, Note : Thus when R a is negligible, θ = 90 o for maximum power developed. The corresponding torque is called pull out torque. 1.1 The Value of Maximum Power Developed        The value of maximum power developed can be obtained by substituting θ = δ in the equation of P m .        When R a is negligible,     θ = 90 o  and cos (θ) = 0 hence, . . .               R a = Z s cosθ   and X s = Z s sinθ        Substituting   cosθ = R a /Z s in equation (6b) we get,         Solving the above quadratic in E b we get,        As E b is completely dependent on excitation, the equation (8) gives the excitation limits for any load for a synchronous motor. If the excitation exceeds this limit, the motor falls out of step. 1.2 Condition for Excitation When Motor Develops ( P m ) R max        Let us find excitation condition for maximum power developed. The excitation

Electrical Engineering interview questions and answers Part 17

Why star delta starter is preferred with induction motor? Star delta starter is preferred with induction motor due to following reasons: • Starting current is reduced 3-4 times of the direct current due to which voltage drops and hence it causes less losses. • Star delta starter circuit comes in circuit first during starting of motor, which reduces voltage 3 times, that is why current also reduces up to 3 times and hence less motor burning is caused. • In addition, starting torque is increased and it prevents the damage of motor winding. State the difference between generator and alternator Generator and alternator are two devices, which converts mechanical energy into electrical energy. Both have the same principle of electromagnetic induction, the only difference is that their construction. Generator persists stationary magnetic field and rotating conductor