EQUIVALENT CIRCUIT

Figure 1.32 shows the equivalent circuit of a single-phase transformer having load impedance ZL. Figure 1.33 is the equivalent circuit of Figure 1.32. The secondary winding resistance (R2), leakage reactance (X2) and load impedance (ZL) connected to secondary terminal is transferred to primary side.
images
Figure 1.32 Equivalent Circuit
images
Figure 1.33 Exact Equivalent Circuit
images
Figure 1.34 Approximate Equivalent Circuit
Since I0 is small compared to full-load current, we can shift the excitation circuit towards the terminal voltage side shown in Figure 1.34. Figure 1.34 is the approximate equivalent circuit, whereas Figure 1.33 is the exact equivalent circuit of Figure 1.32.
From Figure 1.33, the total input impedance between input terminals becomes
images
where images
and images is the impedance of the exciting circuit.
images
R0, X0, R01 and X01 are the four important parameters of the transformer. From open circuit and short circuit test of a transformer, R0, X0 and R01, X01 can be determined respectively.

Comments

Popular posts from this blog

Demagnetising and Cross Magnetizing Conductors

The conductors which are responsible for producing demagnetizing and distortion effects are shown in the Fig.1. Fig. 1        The brushes are lying along the new position of MNA which is at angle θ  from GNA. The conductors in the region AOC = BOD = 2θ  at the top and bottom of the armature are carrying current in such a direction as to send the flux in armature from right to left. Thus these conductors are in direct opposition to main field and called demagnetizing armature conductors.         The remaining armature conductors which are lying in the region AOD and BOC carry current in such a direction as to send the flux pointing vertically downwards i.e. at right angles to the main field flux. Hence these conductors are called cross magnetizing armature conductors which will cause distortion in main field flux.        These conductors are shown in the Fig. 2 Fig. 2  ...

Characteristics of Separately Excited D.C. Generators

The characteristics is separately excited d.c. generator are divided into two types, 1) Magnetization   and         2) Load characteristics. 1.1 Magnetization or Open Circuit Characteristics         The arrangement to obtain this characteristics is shown in the Fig. 1. Fig. 1  Obtaining O.C.C. of separately excited generator        The rheostat as a potential driver is used to control the field current and the flux. It is varied from zero and is measured on ammeter connected.        E o  = (ΦPNZ) / (60A)        As I f is varied, then Φ change and hence induced e.m.f. E o  also varies. It is measured on voltmeter connected across armature. No Load is connected to machine, hence characteristics are also called no load characteristics which is graph of E o  against field current I f as sho...

Armature Voltage Control Method or Rheostatic Control of dc motor

Speed Control of D.C. Shunt Motor (Part2)  2. Armature Voltage Control Method or Rheostatic Control        The speed is directly proportional to the voltage applied across the armature. As the supply voltage is normally constant, the voltage across the armature can be controlled by adding a variable resistance in series with the armature as shown in the Fig. 1. Fig. 1 Rheostat control of shunt motor        The field winding is excited by the normal voltage hence I sh is rated and constant in this method. Initially the reheostat position is minimum and rated voltage gets applied across the armature. So speed is also rated. For a given load, armature current is fixed. So when extra resistance is added in the armature circuit, I a remains same and there is voltage drop across the resistance added ( I a R). Hence voltage across the armature decreases, decreasing the speed below normal value. By varyi...