Parallel Operation of DC Generators

In case of d.c. generating stations, there are heavy thick copper bars which acts as positive and negative terminals for the entire stations. These bars are called bus bars. While connecting the d.c. generators in parallel, the positive and negative terminals of the generators should be respectively connected to the positive and negative terminals of bus bars. If the generator is connected with reverse polarity to the bars, it results in short circuit which will cause damage to the commutators and brushes, ultimately shutting down the station. Before making the parallel operation, it should be checked for reversal polarity for the generators otherwise breakers are tripped off as a result of heavy fault current.
       Consider the bus bar with positive and negative terminals as shown in the Fig. 1. The generators are connected to these bus bars for parallel operation.
Fig. 1 
       The generator 1 is connected to the bus bars and supplying to the load. Now generator 2 is to be connected in parallel.
       The prime mover of the generator 2 is started and its speed is adjusted to the rated value. Then the switch S4 is closed. The voltmeter connected across the open switch S2 completes the circuit. Now the excitation of the generator 2 is adjusted with the help of field rheostat till the voltmeter reads zero. The zero on the voltmeter ensures that the voltage of incoming generator 2 is same as that of generator 1 or the bus bar voltage. The switch S2 is then closed which connects the incoming generator 2 in parallel with the system.
       Under these conditions, the generator 2 will not take any load as its induced e.m.f. is same as bus bar voltage and there will not be any flow of current between two points at same potential. This generator is thus said to be floating on bus bars.
       In order that the generator 2 should supply current, it is necessary that its induced e.m.f. should be more than the bus bar voltage. If E is induced e.m.f. and V is bus bar voltage then the current supplied I is given by,
       To increase the induced e.m.f. of incoming generator 2 its field is strengthened till it takes proper share of load. At the same time the field of generator 1 is weakened to maintain the bus bar voltage constant.
       In summary, following procedure should be adopted while paralleling the d.c. generators :
1. The generator which is to be connected in parallel is called incoming generator. Start the prime mover of incoming generator and adjust its speed to rated value.
2. Close the disconnected switch of the incoming generator.
3. The excitation of the incoming generator is then adjusted till it is few volts more than bus bar voltage.
4. Close the breaker of the incoming generator.
5. The shunt field rheostat of the incoming generator is adjusted to increase its voltage while the field rheostats of already connected generators are adjusted to lower their voltages till the desired load distribution which is indicated by ammeters is achieved.

Comments

Popular posts from this blog

Transformer multiple choice questions part 1

Hello Engineer's Q.[1] A transformer transforms (a) frequency (b) voltage (c) current (d) voltage and current Ans : D Q.[2] Which of the following is not a basic element of a transformer ? (a) core (b) primary winding (c) secondary winding (d) mutual flux. Ans : D Q.[3] In an ideal transformer, (a) windings have no resistance (b) core has no losses (c) core has infinite permeability (d) all of the above. Ans : D Q.[4] The main purpose of using core in a transformer is to (a) decrease iron losses (b) prevent eddy current loss (c) eliminate magnetic hysteresis (d) decrease reluctance of the common magnetic circuit. Ans :D Q.[5] Transformer cores are laminated in order to (a) simplify its construction (b) minimize eddy current loss (c) reduce cost (d) reduce hysteresis loss. Ans : B Q.[6] A transformer having 1000 primary turns is connected to a 250-V a.c. supply. For a secondary voltage of 400 V, the number of secondary turns should be (a) 1600 (b) 250 (c) 400 (d) 1250 A...

Condition for Maximum Power Developed In Synchronous Motor

The value of δ for which the mechanical power developed is maximum can be obtained as, Note : Thus when R a is negligible, θ = 90 o for maximum power developed. The corresponding torque is called pull out torque. 1.1 The Value of Maximum Power Developed        The value of maximum power developed can be obtained by substituting θ = δ in the equation of P m .        When R a is negligible,     θ = 90 o  and cos (θ) = 0 hence, . . .               R a = Z s cosθ   and X s = Z s sinθ        Substituting   cosθ = R a /Z s in equation (6b) we get,         Solving the above quadratic in E b we get,        As E b is completely dependent on excitation, the equation (8) gives the excitation limits for a...

Armature Voltage Control Method or Rheostatic Control of dc motor

Speed Control of D.C. Shunt Motor (Part2)  2. Armature Voltage Control Method or Rheostatic Control        The speed is directly proportional to the voltage applied across the armature. As the supply voltage is normally constant, the voltage across the armature can be controlled by adding a variable resistance in series with the armature as shown in the Fig. 1. Fig. 1 Rheostat control of shunt motor        The field winding is excited by the normal voltage hence I sh is rated and constant in this method. Initially the reheostat position is minimum and rated voltage gets applied across the armature. So speed is also rated. For a given load, armature current is fixed. So when extra resistance is added in the armature circuit, I a remains same and there is voltage drop across the resistance added ( I a R). Hence voltage across the armature decreases, decreasing the speed below normal value. By varyi...