EMF EQUATION OF A TRANSFORMER

Figure 1.22 shows the representation of alternating flux, varying sinusoidally, which increases from its zero value to maximum value (Φm) in one-quarter of the cycle, that is in one-fourth of a second where f is the frequency of AC input in hertz.
The average rate of change of flux is given by images, that is 4m Wb/s or V.
images
Figure 1.22 Representation of Alternating Flux
This rate of change of flux per turn is the induced emf in V.
Therefore, average emf/turn = 4mm V.
Let N1 and N2 be the number of turns in primary and secondary.
images
The rms value of induced emf in primary winding is given by
E1 = (4.44m m) × N1 = 4.44m mN = 4.44f BmArN1 (1.1)
where images is the maximum value of flux density having unit Tesla (T) and Ar is the area of cross-section.
Similarly, RMS value of induced emf in secondary winding is
E 2 = (4.44fΦm )x N2 = 4.44mN2 = 4.44f BmArN2 (1.2)
From Equations (1.1) and (1.2), we have
images
i.e., images
where ‘a’ is the turns ratio of the transformer,
i.e., images
Equation (1.3) shows that emf induced per turn in primary and secondary windings are equal.
In an ideal transformer at no load, V1 = E1 and V2 = E2, where V2 is the terminal voltage of the transformer. Equation (1.3) becomes
images
Example 1.1 The voltage ratio of a single-phase, 50 Hz transformer is 5,000/500 V at no load. Calculate the number of turns in each winding if the maximum value of the flux in the core is 7.82 mWb.
Solution
Here
E1 = V1 = 5,000 V
E2 = V2 = 500 V
φmax = 7.82 m Wb = 7.82 × 10−3 Wb, f = 50Hz
Let N1 and N2 be the number of turns of the primary and secondary windings, respectively.
Since
E1 = 4.44 f φmN1
images
i.e., images
Again, images
images

Comments

  1. This comment has been removed by the author.

    ReplyDelete
  2. If you enjoy exploring semiconductor topics, circuits, and engineering basics, you may want to check out best and trusted electronics concepts and component explanations

    ReplyDelete

Post a Comment

Comment Policy
We’re eager to see your comment. However, Please Keep in mind that all comments are moderated manually by our human reviewers according to our comment policy, and all the links are nofollow. Using Keywords in the name field area is forbidden. Let’s enjoy a personal and evocative conversation.

Popular posts from this blog

Demagnetising and Cross Magnetizing Conductors

The conductors which are responsible for producing demagnetizing and distortion effects are shown in the Fig.1. Fig. 1        The brushes are lying along the new position of MNA which is at angle θ  from GNA. The conductors in the region AOC = BOD = 2θ  at the top and bottom of the armature are carrying current in such a direction as to send the flux in armature from right to left. Thus these conductors are in direct opposition to main field and called demagnetizing armature conductors.         The remaining armature conductors which are lying in the region AOD and BOC carry current in such a direction as to send the flux pointing vertically downwards i.e. at right angles to the main field flux. Hence these conductors are called cross magnetizing armature conductors which will cause distortion in main field flux.        These conductors are shown in the Fig. 2 Fig. 2  ...

Characteristics of Separately Excited D.C. Generators

The characteristics is separately excited d.c. generator are divided into two types, 1) Magnetization   and         2) Load characteristics. 1.1 Magnetization or Open Circuit Characteristics         The arrangement to obtain this characteristics is shown in the Fig. 1. Fig. 1  Obtaining O.C.C. of separately excited generator        The rheostat as a potential driver is used to control the field current and the flux. It is varied from zero and is measured on ammeter connected.        E o  = (ΦPNZ) / (60A)        As I f is varied, then Φ change and hence induced e.m.f. E o  also varies. It is measured on voltmeter connected across armature. No Load is connected to machine, hence characteristics are also called no load characteristics which is graph of E o  against field current I f as sho...

Armature Voltage Control Method or Rheostatic Control of dc motor

Speed Control of D.C. Shunt Motor (Part2)  2. Armature Voltage Control Method or Rheostatic Control        The speed is directly proportional to the voltage applied across the armature. As the supply voltage is normally constant, the voltage across the armature can be controlled by adding a variable resistance in series with the armature as shown in the Fig. 1. Fig. 1 Rheostat control of shunt motor        The field winding is excited by the normal voltage hence I sh is rated and constant in this method. Initially the reheostat position is minimum and rated voltage gets applied across the armature. So speed is also rated. For a given load, armature current is fixed. So when extra resistance is added in the armature circuit, I a remains same and there is voltage drop across the resistance added ( I a R). Hence voltage across the armature decreases, decreasing the speed below normal value. By varyi...