Speed Control of D.C. Series Motor : Flux Control

Speed Control of D.C. Series Motor (Part1)      

       The flux produced by the winding depends on the m.m.f. i.e. magnetomotive force which is the product of current and the number of turns of the winding through which current is passing. So flux can be changed either by changing the current by adding a resistance or by changing the number of turns of the winding. Let us study the various methods based on this principle.

1. Flux Control
       The various methods of flux control in a d.c. series motor are explained below :
1.1 Field Divertor Mehtod
       In this method the series field winding is shunted by a variable resistance () known as field divertor. The arrangement is shown in the Fig. 1(a).
       Due to the parallel path of Rx , by adjusting the value of Rx, any amount of current can be diverted through the divertor. Hence current through the field winding can be adjusted as per the requirement. Due to this, the flux gets controlled and hence the speed of the motor gets controlled.
       By this method the speed of the motor can be controlled above rated value. The speed armature current characteristics with range in Rx is shown in the Fig. 1(b).
Fig. 1
1.2 Armature Divertor Method
       This method is used for the motor which require constant load torque. An armature of the motor is shunted with an external variable resistance (Rx) as shown in the Fig. 2. This resistance Rx is called armature divertor.
Fig. 2  Armature divertor
       Any amount of armature current can be diverted through the divertor. Due to this , armature current reduces. But as T α Φ Ia and load torque is constant, the flux is to be increased. So current through field winding increases, so flux increases and speed of the motor reduces. The method is used to control the speed below the normal value.
1.3 Tapped Field Method
       In this method, flux change is achieved by changing the number of turns of the field winding. The field winding is provided with the taps as shown in the Fig. 3.
Fig. 3  Tapped field
       The selector switch 'S' is provided to select the number of turns (taps) as per the requirement. When the switch 'S' is in position 1 the entire filed winding is in the circuit and motor runs with normal speed. As switch is moved from position 1 to 2 and onwards, the number of turns of the field winding in the circuit decreases. Due to this m.m.f. require to produce the flux, decreases. Due to this flux produced decreases, increasing the speed of the motor above rated value. The method is often used in electric traction.
1.4 Series - Parallel Connection of Field
       In this method, the field coil is divided into various parts. These parts can then be connected in series or parallel as per the requirement. The Fig. 4(a) and (b) show the two parts of field coil connected in series and parallel.
Fig. 4  Series parallel grouping of field coils
        For the same torque, if the field coil is arranged in series or parallel, m.m.f. produced by the coils changes, hence the flux produced also changes. Hence speed can be controlled. Some fixed speeds only can be obtained by parallel grouping, the m.m.f. produced decreases, hence higher speed can be obtained by parallel grouping. The method is generally used in case of fan motors.

Comments

Popular posts from this blog

Practical Commutation

The e.m.f. induced in each coil of armature is alternating in nature. If load is connected, the current flowing will also be alternating. But the flow of current in a d.c. generator must be undirectional. This can be achieved by the use of commutator. When the armature conductors are under the influence of one pole they carry current in one direction whereas the current is reversed when the conductors are under the influence of other pole. This reversal of current takes place along the magnetic neutral axis. Fig. 1 Note : The reversal of current is likely to take place in short interval when a coil is short circuited by a brush so that transfer of current from one direction to other is carried out without any sparking. This process is called commutation.        Thus a process by which current in the short circuited coil is reversed while it crosses the MNA is called commutation. The time during which the coil remains short circuited is known as...

Demagnetising and Cross Magnetizing Conductors

The conductors which are responsible for producing demagnetizing and distortion effects are shown in the Fig.1. Fig. 1        The brushes are lying along the new position of MNA which is at angle θ  from GNA. The conductors in the region AOC = BOD = 2θ  at the top and bottom of the armature are carrying current in such a direction as to send the flux in armature from right to left. Thus these conductors are in direct opposition to main field and called demagnetizing armature conductors.         The remaining armature conductors which are lying in the region AOD and BOC carry current in such a direction as to send the flux pointing vertically downwards i.e. at right angles to the main field flux. Hence these conductors are called cross magnetizing armature conductors which will cause distortion in main field flux.        These conductors are shown in the Fig. 2 Fig. 2  ...

Winding Pitches

Now we will consider the definitions of different types of winding pitches, required in the design of the armature winding. 1.1 Back Pitch         The distance which is measured interns of armature conductors i.e. between top and bottom coil sides of a coil measured around the back of the armature i.e. away from the commutator is called back pitch and is denoted by . It is measured interms of coil sides. Note : Since it is difference between odd and even number, it is always odd number.        The size of the coil is decided by the back pitch. The back pitch is normally equal to coilsides per pole. It is shown for lap and wave type of winding in the Fig. 1. Fig. 1        The back pitch for the winding shown in the Fig. 1 is y b = 14 - 1 = 13 as coilsides 1and 14 are of coil number 1. 1.2 Front Pitch        It is defined as the distance measured between two c...