Characteristics of D.C. Generators

The d.c. generators have following characteristics in general,
1) Magnetization characteristics
2) Load characteristics
1.1 Magnetization Characteristics
       This characteristics is the graph of generated no load voltage E against the field current If, when speed of, generator is maintained constant. As it is plotted without load with open output terminals it is also called No load characteristics or Open circuit characteristics.
       Eo Vs Iis magnetization characteristics
       Where  Eo = No load induced e.m.f.
       But for generator,
       E = (ΦPNZ)/(60A)
...     E α   Φ                 with (PNZ) / (60A)  constant
...     α   If                    as   Φ  α   If
       Thus induced e.m.f. increases directly as I increases. But after certain I core gets saturated and flux also remain constant though Iincreases. Hence after saturation, voltage also remains constatnt.
Note : Thus characteristics is linear till saturation and after that bends such that voltage remains constant though I increases.
        The characteristics is shown in the Fig. 1.
Fig. 1  Magnetization characteristics
       Now the induced e.m.f. also varies with speed.
       Actually,             E   α   N Φ
       So if magnetization characteristics for various speeds are plotted we will get family of parallel characteristics as shown in the Fig. 2. For lower speeds, generated voltages are less so characteristics for lower speeds are below the characteristics for higher speeds.
Fig. 2
1.2 Load Characteristics
       These are further divided into two categories,
1) External characteristics
2) Internal characteristics
       The external characteristics is the graph of the terminal voltage Vt against load current IL.
       The internal characteristics is the graph of the generated induced e.m.f. against the armature current Ia.
Note : While plotting both the characteristics, the speed N of the generator is maintained constant.
Note : In most of the cases, the shunt field current is very small as compared with load current IL. Hence in practice, the internal characteristics shows the graph of induced e.m.f. E against load current IL, instead of Ia, neglecting Ish.

Comments

Popular posts from this blog

Practical Commutation

The e.m.f. induced in each coil of armature is alternating in nature. If load is connected, the current flowing will also be alternating. But the flow of current in a d.c. generator must be undirectional. This can be achieved by the use of commutator. When the armature conductors are under the influence of one pole they carry current in one direction whereas the current is reversed when the conductors are under the influence of other pole. This reversal of current takes place along the magnetic neutral axis. Fig. 1 Note : The reversal of current is likely to take place in short interval when a coil is short circuited by a brush so that transfer of current from one direction to other is carried out without any sparking. This process is called commutation.        Thus a process by which current in the short circuited coil is reversed while it crosses the MNA is called commutation. The time during which the coil remains short circuited is known as...

Demagnetising and Cross Magnetizing Conductors

The conductors which are responsible for producing demagnetizing and distortion effects are shown in the Fig.1. Fig. 1        The brushes are lying along the new position of MNA which is at angle θ  from GNA. The conductors in the region AOC = BOD = 2θ  at the top and bottom of the armature are carrying current in such a direction as to send the flux in armature from right to left. Thus these conductors are in direct opposition to main field and called demagnetizing armature conductors.         The remaining armature conductors which are lying in the region AOD and BOC carry current in such a direction as to send the flux pointing vertically downwards i.e. at right angles to the main field flux. Hence these conductors are called cross magnetizing armature conductors which will cause distortion in main field flux.        These conductors are shown in the Fig. 2 Fig. 2  ...

Armature Voltage Control Method or Rheostatic Control of dc motor

Speed Control of D.C. Shunt Motor (Part2)  2. Armature Voltage Control Method or Rheostatic Control        The speed is directly proportional to the voltage applied across the armature. As the supply voltage is normally constant, the voltage across the armature can be controlled by adding a variable resistance in series with the armature as shown in the Fig. 1. Fig. 1 Rheostat control of shunt motor        The field winding is excited by the normal voltage hence I sh is rated and constant in this method. Initially the reheostat position is minimum and rated voltage gets applied across the armature. So speed is also rated. For a given load, armature current is fixed. So when extra resistance is added in the armature circuit, I a remains same and there is voltage drop across the resistance added ( I a R). Hence voltage across the armature decreases, decreasing the speed below normal value. By varyi...